ABB SPAA 341 C Feeder Protection Relay
ABB SPAA 341 C Feeder Protection Relay Supplier and Exporter in India
ABB SPAA 341 C Relay Replacement with REX615
Replacement: ABB SPAA 341 C is discontinued and is supported under ABB’s SPACOM-to-REX615 retrofit program. The existing relay version, order code and panel details should be checked before proceeding with the retrofit.
ARP IMPEX supplies and exports ABB SPAA 341 C feeder protection relays for replacement, maintenance spares and existing medium-voltage protection panels.
SPAA 341 C belongs to ABB’s older SPACOM feeder protection range. It was used mainly on radial distribution feeders in isolated-neutral, resistance-earthed and resonant-earthed networks. The relay combines overcurrent, short-circuit, earth-fault and phase discontinuity protection, with autoreclosing available on the appropriate versions.
Unlike simpler feeder relays, SPAA 341 C was supplied in several configurations. Depending on the version, the relay could include conventional overcurrent and earth-fault protection, directional earth-fault protection and an autoreclose module.
This makes the exact model important when replacing an old unit. A buyer asking for only “SPAA 341 C” may have a C1, C2, C3, C4 or C5 configuration installed.
ABB lists SPAA 341 C as not active since 2009. Most current enquiries are therefore for a failed relay, a matching spare for old switchgear, plant shutdown stock or replacement through ABB’s REX615 retrofit program.
If you are looking for ABB SPAA 341 C price, replacement or availability from India, send the complete order number and a clear nameplate photograph so the correct version can be checked before quotation.
Technical Specifications
- Brand: ABB
- Series: SPACOM / SPAA
- Model: SPAA 341 C
- Product type: Feeder protection relay
- Product status: Legacy / discontinued
- Main use: Medium-voltage radial feeder protection
- Overcurrent protection: Available
- Short-circuit protection: Available
- Earth-fault protection: Directional and non-directional functions depending on
- configuration
- Residual overvoltage protection: Available
- Phase discontinuity protection: Available
- Phase current inputs: 1 A / 5 A
- Directional earth-fault current inputs: 0.2 A / 1 A
- Residual voltage input: 100 V / 110 V / 120 V
- Rated frequency: 50 Hz or 60 Hz depending on order number
- Autoreclose: Up to five successive shots on equipped versions
- Circuit-breaker failure protection: Available
- Circuit-breaker condition monitoring: Available with autoreclose module
- Communication: Fibre-optic SPA serial bus
- Auxiliary supply: 80–265 V AC/DC or 18–80 V DC depending on version
- Enclosure protection: IP54
For replacement work, the full RS 614 order code should always be checked because the installed functions and auxiliary supply can differ.
Features
- Three-phase overcurrent protection
- Short-circuit protection
- Non-directional earth-fault protection
- Directional earth-fault protection on applicable versions
- Residual overvoltage protection
- Phase discontinuity supervision
- Circuit-breaker failure protection
- Multi-shot circuit-breaker autoreclosing
- Circuit-breaker condition monitoring
- External blocking and control inputs
- Trip and signalling outputs
- SPA communication with higher-level systems
- Internal hardware and software self-supervision
These functions vary between SPAA 341 C versions, which is why the exact suffix should be confirmed before sourcing a replacement.
Applications
SPAA 341 C was commonly used for:
- Medium-voltage feeder protection
- Radial distribution feeders
- Industrial distribution networks
- Utility substations
- Isolated-neutral networks
- Resistance-earthed networks
- Resonant-earthed networks
- Directional earth-fault protection
- Short-circuit protection
- Feeder phase-unbalance supervision
- Circuit-breaker autoreclosing
- Existing ABB SPACOM switchgear
- Plant maintenance spares
- Shutdown replacement requirements
ABB specifically identifies the relay for radial feeders in isolated-neutral, resistively earthed and resonant-earthed networks.
ABB SPAA 341 C Models
SPAA 341 C is a product family with several configurations. This is important for buyers looking for a matching legacy relay.
ABB SPAA 341 C
The complete version, supplied with the overcurrent/earth-fault protection module, directional earth-fault module and autoreclose module.
Main order-number group: RS 614 080.
ABB SPAA 341 C1
Supplied without the autoreclose module.
Main order-number group: RS 614 081.
ABB SPAA 341 C2
Supplied without the directional earth-fault module, while retaining the main overcurrent/earth-fault protection and autoreclose functions.
Main order-number group: RS 614 082.
ABB SPAA 341 C3
Supplied without the directional earth-fault module and without the autoreclose module.
Main order-number group: RS 614 083.
ABB SPAA 341 C4
This version does not include the main overcurrent/non-directional earth-fault module. It retains the directional earth-fault and autoreclose sections.
Main order-number group: RS 614 084.
ABB SPAA 341 C5
This is the more limited configuration without the main overcurrent/earth-fault module and without the autoreclose module, leaving the directional earth-fault protection section.
Main order-number group: RS 614 085.
Versions supplied with the RTXP 18 test adapter used the corresponding RS 614 280 to RS 614 285 order-number groups.
For a replacement enquiry, please specify whether the installed relay is SPAA 341 C, C1, C2, C3, C4 or C5.
ABB SPAA 341 C Replacement
Since ABB discontinued SPAA 341 C, current requirements normally come from existing switchgear installations.
Buyers may need:
- Replacement for a failed SPAA 341 C
- Matching SPAA 341 C1, C2, C3, C4 or C5
- Legacy SPACOM maintenance spare
- Emergency feeder relay replacement
- Plant shutdown stock
- Spare for existing switchgear
- Retrofit of an ageing feeder protection panel
For an exact legacy relay, please send:
- Complete ABB order number
- Relay model and suffix
- Clear nameplate photograph
- Required quantity
- Destination country
- Required delivery date
ABB SPAA 341 C to REX615 Retrofit
ABB officially lists SPAA 341 C among the SPACOM relay types supported by its SPACOM-to-REX615 Relay Retrofit Program.
ABB’s retrofit solution includes the REX615 relay, retrofit connector kit and documentation. ABB also provides options for configuration and installation support. The program is intended to simplify replacement of supported SPACOM relays and reduce the amount of panel rewiring normally required during a relay upgrade.
A retrofit may be considered when:
- SPAA 341 C has failed
- Legacy spare availability is becoming difficult
- Several SPACOM relays are being replaced
- The existing feeder panel is being upgraded
- Long-term relay support is preferred
Because SPAA 341 C was supplied in several configurations, the exact installed model and panel arrangement should be checked before selecting the retrofit configuration.
Why Buy ABB SPAA 341 C from ARP IMPEX?
ARP IMPEX supports buyers looking for ABB legacy protection relays for existing substations, plants and switchgear.
We can assist with:
- ABB SPAA 341 C part-code checking
- SPAA 341 C1 to C5 identification
- Nameplate matching
- Legacy relay availability
- Replacement for failed SPAA 341 C relays
- REX615 retrofit enquiries
- Single-unit and multiple-quantity quotations
- Plant maintenance and shutdown spares
- ABB technical documentation
- Export packing
- International shipping
We handle enquiries from utilities, power plants, EPC contractors, industrial companies, panel builders, maintenance companies and electrical traders.
Request a Quote for ABB SPAA 341 C
For ABB SPAA 341 C price and availability, please send:
- Complete ABB SPAA 341 C order number
- Exact version – C, C1, C2, C3, C4 or C5
- Clear relay nameplate photograph
- Quantity required
- Destination country
- Required delivery date
If the order code is not readable, send us a clear photograph of the relay nameplate and front panel.
Send your ABB SPAA 341 C part code, quantity and destination country to ARP IMPEX for legacy spare availability, replacement or REX615 retrofit quotation.
Related products
-

Schneider Electric Easergy MiCOM P142 Numerical Feeder Management Protection Relay
-

Schneider Electric Easergy MiCOM P145 Numerical Feeder Management Protection Relay
-

Schneider Electric PowerLogic™ MiCOM P130C Feeder Management and Frequency Protection Relay
-

Schneider Electric PowerLogic™ MiCOM P114D Feeder Protection Relay